Skip to main content
Knowledge CenterEngineeringCompressed Air Purity

Engineering · 10 min

Compressed Air Purity

ISO 8573-1 Quality Classes, Contamination Measurement, and System Design

Compressed air contains particles, liquid water, water vapour, and oil aerosols and vapour introduced during compression and distribution. ISO 8573-1 defines quality classes for each contaminant type, providing a standardised specification language for compressed air systems. Achieving the correct purity class requires understanding contamination sources, measurement methods, and the filtration and drying technologies that control each contaminant type.

≤0.01 mg/m³

ISO 8573-1 Class 1 oil

≤ −70°C

Class 1 pressure dew point

Zero permitted

Class 1 particles (≥5 µm)

+2°C to +10°C

Refrigerant dryer PDP

01 /

ISO 8573-1 Quality Classes

ISO 8573-1 defines quality classes 0 through 6 for three contamination categories independently: solid particles (by count and size), moisture (by pressure dew point, °C), and total oil (aerosol plus vapour, mg/m³). Class 0 is specified by the user and is more stringent than Class 1 — it is not a defined numerical value in the standard. Class 1 is the highest standard-defined purity; Class 6 is the least stringent. A compressed air quality specification written as ISO 8573-1:2010 [2:4:2] means Class 2 for particles, Class 4 for moisture, and Class 2 for oil. Each class must be specified independently because different treatment stages address each contamination type — a highly efficient particulate filter provides no benefit for dew point, and a refrigerant dryer reduces moisture but does not remove oil aerosols.

User-defined, more stringent than Class 1

Class 0

≤0.01 mg/m³ (total oil)

Class 1 oil content

ISO 8573-1 [2:4:2] = particles:moisture:oil

Notation example

02 /

Particle Quality Classes

ISO 8573-1 particle classes are defined by the maximum number of particles per cubic metre at specified size ranges. Class 1 (particles): ≤20,000 particles/m³ at 0.1–0.5 µm; ≤400 at 0.5–1 µm; ≤10 at 1–5 µm; no particles ≥5 µm. Class 2: same ≤400,000 at 0.1–0.5 µm; ≤6,000 at 0.5–1 µm; ≤100 at 1–5 µm; no particles ≥5 µm. Class 3: no limit for <1 µm; ≤1,000 at 1–5 µm; no particles ≥5 µm. Classes 4 and 5 allow particles ≥5 µm in increasing quantities. Class 6 allows particle mass concentration up to 10 mg/m³ without size distribution limits. For most industrial pneumatic actuator and tool applications, particle Class 3 or 4 is adequate. Instrument air (analytical instruments, pressure transmitters, control valves) requires particle Class 1 or 2 to prevent instrument blockage and measurement error.

Zero permitted

Class 1 (≥5 µm particles)

≤1,000 particles/m³

Class 3 (1–5 µm)

Class 1 or 2

Instrument air class

03 /

Moisture Classes and Pressure Dew Point

Moisture in compressed air is expressed as pressure dew point (PDP) — the temperature at which condensation occurs at the system operating pressure. A PDP of −40°C at 7 bar means the air contains so little moisture that condensation will not form until the temperature drops to −40°C, even at 7 bar line pressure. ISO 8573-1 moisture classes: Class 1: PDP ≤ −70°C; Class 2: ≤ −40°C; Class 3: ≤ −20°C; Class 4: ≤ +3°C; Class 5: ≤ +7°C; Class 6: ≤ +10°C. Refrigerant dryers achieve PDP between +2°C and +10°C (Classes 4–6). Adsorption (desiccant) dryers achieve PDP between −20°C and −70°C (Classes 1–3). The conversion from PDP to water content in g/m³ at a reference condition allows calculation of absolute humidity: at −40°C PDP and 7 bar, the water content is approximately 0.003 g/m³ — compared to 1.4 g/m³ at +7°C PDP.

≤ −70°C

Class 1 PDP

+2°C to +10°C (Classes 4–6)

Refrigerant dryer PDP range

−20°C to −70°C (Classes 1–3)

Desiccant dryer PDP range

04 /

Oil Content Classes and Measurement

Oil in compressed air originates from lubricant carryover from oil-lubricated compressors (in the form of aerosol and vapour) and from atmospheric hydrocarbon vapours that concentrate during compression. ISO 8573-1 total oil classes (aerosol + liquid + vapour, mg/m³): Class 1: ≤0.01 mg/m³; Class 2: ≤0.1 mg/m³; Class 3: ≤1 mg/m³; Class 4: ≤5 mg/m³. Oil-free compressors (Class 0 equipment per ISO 8573-7) still require oil removal filtration for Class 1 or Class 2 applications because atmospheric hydrocarbon vapours drawn into the compressor inlet concentrate to measurable levels at the outlet. ISO 8573-2 defines the test method for aerosol oil measurement: impaction on a membrane filter with gravimetric analysis. ISO 8573-5 defines the vapour oil measurement method using activated carbon adsorption tubes. Total oil = aerosol (ISO 8573-2 method) + oil vapour (ISO 8573-5 method). Coalescing filters remove aerosol oil to Class 1; activated carbon adsorption removes vapour oil — both stages are required to achieve verified Class 1 compliance.

≤0.01 mg/m³

Class 1 oil content

Coalescing filter (ISO 8573-2)

Aerosol removal

Activated carbon (ISO 8573-5)

Vapour removal

05 /

Contamination Sources During Compression

Ambient air drawn into a compressor contains atmospheric particulates (0.1–10 µm pollen, dust, soot), water vapour (humidity), and trace hydrocarbon vapours. During compression, all constituents are concentrated in proportion to the compression ratio: at 7 bar gauge (8 bar absolute), volume reduces to 1/8 and contaminant mass per volume increases 8-fold. Compressed air after-cooling (required to prevent thermal damage to downstream equipment) causes the compressed, humid air to cool rapidly — water vapour condenses into liquid water and aerosol droplets. The after-cooler and condensate separator remove the largest water fraction (typically 70–90% of the inlet water vapour at tropical ambient conditions) but leave substantial residual moisture requiring drying. Oil-lubricated compressors inject oil into the compression stage for cooling and sealing — oil carryover from the separator and coalescing filter in the compressor unit outlet is typically 1–5 mg/m³ before point-of-use treatment.

06 /

Filtration System Design for Quality Classes

A compressed air treatment train is designed in stages, each addressing one contamination category at the conditions produced by the upstream stage. After-cooler + condensate separator: removes bulk liquid water and coarse aerosols (Stages 4–5 moisture, particle Class 4–5). General purpose coalescing filter (1 µm coalescence element): removes liquid aerosol oil to 0.1 mg/m³ and particles ≥1 µm (particle Class 2–3, oil Class 2–3). High-efficiency coalescing filter (0.01 µm coalescence element): reduces oil aerosol to 0.01 mg/m³ (oil Class 1). Activated carbon adsorber: removes oil vapour below 0.003 mg/m³ (oil Class 1). Desiccant dryer: achieves PDP ≤ −40°C (moisture Class 2). Final particulate filter (PTFE membrane or borosilicate fiber): ensures sterile or classified air downstream of all treatment stages (particle Class 1 or 2). DRYCORE™ filtration systems provide integrated particulate and coalescing elements for compressed air applications, reducing system footprint and pressure drop budget.

Oil Class 2 (0.1 mg/m³)

Coalescing filter achieves

Oil Class 1 (0.01 mg/m³)

High-efficiency coalescer

Vapour removal to full Class 1 compliance

Activated carbon adds

ENGINEERING DIAGRAMS

Compressed Air Treatment Train — ISO 8573-1Sequential compressed air treatment stages: compressor, aftercooler and moisture separator, refrigerant or desiccant dryer, particulate filter (Class 1 dust), coalescing oil mist filter (Class 1 oil), and activated carbon filter (Class 1 hydrocarbons). ISO 8573-1 purity class level achieved at each stage is shown.AMBIENTCOMPRESSORcondensate drainAFTERCOOLER +SEPARATORDESICCANTDRYERDP ≤ −40°CPARTICULATEFILTERISO 8573-1 dustOIL COALESCER(coalescing)ISO 8573-1 oil mistACTIVATEDCARBONhydrocarbonsCLEANAIRClass 1.1.1END USEISO 8573-1 PURITY CLASSES — three-number code: [particles] [water] [oil]Class 1.1.1: ≤0.1µm·mg/m³ · dew point ≤−70°C · ≤0.01mg/m³ oil · highest purityISO 8573-2 specifies test methods for oil content measurementISO 8573-1 · ISO 8573-2
Compressed Air Treatment Train — ISO 8573-1 Purity Classes — Left to right sequence: ambient air inlet, compressor block with triangle pump symbol, aftercooler (sinusoidal coil symb…
VIEW FULL DIAGRAM →
ISO 8573-1 Compressed Air Purity ClassesThree-panel reference chart for ISO 8573-1:2010. Top panel shows solid particle purity classes 0–5 by particle count per cubic metre at ≥0.1 µm, ≥0.5 µm, ≥1 µm, and ≥5 µm. Middle panel shows water content as maximum pressure dew point from Class 1 (−70 °C) to Class 6 (+10 °C). Bottom panel shows total oil content from Class 1 (0.01 mg/m³) to Class 4 (5 mg/m³). Lower class number means tighter / cleaner air.ISO 8573-1:2010 — COMPRESSED AIR PURITY CLASSES← TIGHTER (more stringent)SOLID PARTICLES — MAX COUNT PER m³ AT STATED SIZE RANGECLASS≥0.1 µm≥0.5 µm≥1 µm≥5 µmISO CODE0per specper specper specper specISO 8573-1 Class 0120 000400100ISO 8573-1 Class 12400 0006 0001002ISO 8573-1 Class 2390 0001 00010ISO 8573-1 Class 3410 000500ISO 8573-1 Class 45100 0001 000ISO 8573-1 Class 56–9…(see ISO 8573-1:2010 Table 1 for complete values)WATER CONTENT — MAXIMUM PRESSURE DEW POINT [°C]1−70 °C2−40 °C3−20 °C4+3 °C5+7 °C6+10 °C100 → driest Class 1 (−70 °C) ·····················dryness →····················· wettest Class 6 (+10 °C)TOTAL OIL CONTENT — MAXIMUM [mg/m³]10.01 mg/m³20.1 mg/m³31 mg/m³45 mg/m³Xper spec mg/m³ISO 8573-1:2010
ISO 8573-1 Compressed Air Purity Classes — Three-panel reference chart for ISO 8573-1:2010. Top panel — solid particles: table showing Classes 0–5 with maximum par…
VIEW FULL DIAGRAM →

COMMON ENGINEERING MISTAKES

Specifying ISO 8573-1 Class 0 air quality when the application only requires Class 1 or Class 2. Class 0 requires an inherently oil-free compressor — applying it to systems served by lubricated compressors forces complete system replacement rather than downstream treatment.

Measuring compressed air quality only at the dryer or filter outlet. Compressed air picks up contamination from distribution pipework — point-of-use measurements at the application connection are required to verify actual delivered quality.

Confusing pressure dew point (PDP) with atmospheric dew point. ISO 8573-1 water classes specify PDP at line pressure — a PDP of −40°C at 7 bar corresponds to approximately −27°C atmospheric dew point; the two figures are not interchangeable in specifications.

ENGINEERING REFERENCES

STANDARD

ISO 8573-1:2010, Compressed Air — Part 1: Contaminants and Purity Classes

Primary standard defining contamination classes for particles, water (dewpoint), and oil in compressed air systems.

STANDARD

ISO 8573-2:2018, Compressed Air — Part 2: Test Methods for Aerosol Oil and Particle Content

Test methods for measuring oil aerosol and particle concentration in compressed air at point-of-use sampling.

STANDARD

ISO 8573-3:2010, Compressed Air — Part 3: Test Methods for Measurement of Humidity

Test methods for pressure dewpoint measurement used to verify ISO 8573-1 water class compliance.

STANDARD

ISO 8573-7:2003, Compressed Air — Part 7: Test Methods for Viable Microbiological Contaminants

Microbiological testing standard for breathing air and pharmaceutical-grade compressed air applications.

FREQUENTLY ASKED QUESTIONS

RELATED ENGINEERING TOPICS

Air Intake System Design

Engineering

Airflow Engineering

Engineering

Compressed Air Dryer Selection: Refrigeration, Desiccant, and Membrane Drying Technologies vs ISO 8573-1 Dew Point Classes

engineering

Compressed Air Quality Verification — ISO 8573-4, -5, and -7

Engineering

Crankcase Ventilation and Blow-By Gas Filtration

Engineering

Filter Media Science

Engineering

CITE THIS PAGE

ELIMFILTERS. (2026). Compressed Air Purity: Compressed Air Purity. ELIMFILTERS Engineering Knowledge Platform. https://elimfilters.com/knowledge-center/engineering/compressed-air-purity

We use optional analytics providers, including GA4, PostHog, and Microsoft Clarity, to understand platform usage and improve our services. We do not sell personal information. See our Cookie Policy and Privacy Policy.